The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.
Product Images
Product Videos
Virtual Product Tour (VPT)
Specifications
| Name | Type | Value | Unit Value (Imperial) | Unit Name | Unit Value (Metric) | Unit Name (Metric) |
|---|---|---|---|---|---|---|
| Rating Range | text | 120 to 600V, single phase and three phase @ 50/60 Hz | ||||
| Transfer Type | text | Switch application dependent | ||||
| Switch Type | text | Switch application dependent |
Documents & Spec Sheets
Features & Benefits
Product Features
- Auxiliary relay contacts:
- Source 1 present 2NO and 2NC
- Source 2 present 2NO and 2NC
- Source 1 and source 2 sensing:
- Undervoltage / underfrequency
- Overvoltage / overfrequency
- Three-phase rotation protection
- Three-phase voltage unbalance/loss
- Pre-transfer signal contacts 1NO and 1NC
- Go to emergency (Source 2)
- Seven field-programmable time delays
- LCD-based display for programming, system diagnostic and help message display
- Mimic diagram with source available and connected LED indication
- Time-stamped history log
- System test pushbutton
- Programmable plant exercise (off, daily, 7,14 and 28 day) interval selectable run time 0-600 minutes no load/load with fail-safe
- Integral overcurrent protection (optional)
- In-phase transition
- Stainless steel cover for controller (optional)
- Communications via RS-232 or Modbus through an integrated RS-485 port (optional)
Complete Specifications
Technical Summary
| Name | Type | Value | Unit Value (Imperial) | Unit Name | Unit Value (Metric) | Unit Name (Metric) |
|---|---|---|---|---|---|---|
| Rating Range | text | 120 to 600V, single phase and three phase @ 50/60 Hz | ||||
| Transfer Type | text | Switch application dependent | ||||
| Switch Type | text | Switch application dependent | ||||
| Input Control Voltage | text | 65 to 145 Vac 50/60 hZ | ||||
| Voltage Measurements of Utility | text | Source 1 VAB Source 2 VABSource 1 VAC Source 2 VBCSource 1 VCA Source 2 VCA | ||||
| Voltage Measurement Range | text | 0 to 790 VAC rms (50/60 Hz) | ||||
| Voltage Measurement Accuracy | text | +/-2% of nominal input voltage | ||||
| Frequency Measurements Of | text | Source 1 and Source 2 | ||||
| Frequency Measurement Range | text | 40 Hz to 70 Hz | ||||
| Frequency Measurement Accuracy | text | +/- 0.1 Hz | ||||
| Undervoltage Dropout | text | 50% to 90% of nominal voltage | ||||
| Undervoltage Pickup | text | (Dropout +2%) to 99% of the nominal system voltage | ||||
| Underfrequency Dropout Range | text | 90 to 97% of the nominal system frequency | ||||
| Underfrequency Pickup Range | text | (Dropout +1 Hz) to 99% of the nominal system frequency | ||||
| Overfrequency Dropout Range | text | 103 to 110% of the nominal system frequency | ||||
| Overfrequency Pickup Range | text | 101% to (dropout - 1 Hz) of the nominal system frequency | ||||
| Operating Temperature Range | text | -20 to 70 degree C (-4 to +158 degree F) | ||||
| Storage Temperature Range | text | -30 to 85 degree C (-22 to +185 degree F) | ||||
| Operating Humidity | text | 0 to 95% relative humidity (noncondensing) | ||||
| Operating Environment | text | Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons | ||||
| Generator Start Relay | text | 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load | ||||
| K1, K2 Relays | text | 10A, 1-3 hp @ 250 Vac10A@30 Vdc | ||||
| Applicable Testing | text | UL-recognized componentMeets intent of UL 991 & UL 1008Meets IEC 1000-4-2, 1000-4-3, 1000-4-4 | ||||
| Applicable Testing Continued | text | 1000-4-5, 1000-4-6, 1000-4-11CISPR 11, Class AFCC Part 15, Class ACSS 22.2-178 | ||||
| Enclosure Compatibility | text | NEMA 1, NEMA 3R and NEMA 12UV-resistant ATC-300+ faceplate |