C175-20 (60 Hz)

C175-20

Producing reliable power from 3150 - 4000 ekW at 60 Hz, our C175-20 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The generator set is certified for low fuel consumption, U.S. EPA Stationary Emergency Use only.

Product Images

Product Videos

Virtual Product Tour (VPT)

Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Standby Ratingtext4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Ratingtext3600 (no fan)/3500/3300 (no fan)/3180 ekW
Emissions/Fuel StrategytextLow Fuel, Tier 2

View All Specifications (25)

Documents & Spec Sheets

Electric Power Rating Guide

Download

C175-20, 60 Hz, 3500 ekW Standby/MC, 3180 ekW Prime U.S. EPA Stationary Emergency (Tier 2) (with fan) Spec Sheet

Download

C175-20, 60 Hz, 3900 ekW Standby/MC, 3500 ekW Prime, 3150 ekW Cont., Low Fuel Consumption (with fan) Spec Sheet

Download

C175-20, 60 Hz, 3900 ekW Standby/MC, 3500 ekW Prime, 3150 ekW Cont. U.S. EPA Stationary Emergency (Tier 2) (with fan) Spec Sheet

Download

C175-20, 60 Hz, 4000 ekW Standby/MC, 3600 ekW Prime, 3250 ekW Cont., Low Fuel Consumption (without fan) Spec Sheet

Download

C175-20, 60 Hz, 3620 ekW Standby/MC, 3300 ekW Prime U.S. EPA Stationary Emergency (Tier 2) (without fan) Spec Sheet

Download

C175-20 60 Hz 4000 ekW Standby/MC, 3600 ekW Prime, 3250 ekW Cont., US. EPA Stationary Emergency (Tier 2) (without fan) Spec Sheet

Download

C175-20, 60 Hz, 3180 ekW, Prime-DCP, U.S. EPA Stationary Emergency Use Only (Tier 2) (with fan) Spec Sheet

Download

C175-20, 60 Hz, 3500 ekW, Prime-DCP, U.S. EPA Stationary Emergency Use Only (Tier 2) (with fan) Spec Sheet

Download

C175-20, 60 hz, 3300 ekW Prime-DCP, Low Fuel Consumption (without fan) Spec Sheet

Download

C175-20, 60 Hz, 3500 ekW, Prime-DCP, U.S. EPA Stationary Emergency Use Only (Tier 2) (with fan) Spec Sheet

Download

C175-20, 60 Hz, 3600 ekW, Prime-DCP, Low Fuel Consumption (without fan) Spec Sheet

Download

C175-20, 60 Hz, 3600 ekW, Prime-DCP, U.S. EPA Stationary Emergency Use Only (Tier 2) (without fan) Spec Sheet

Download

Features & Benefits

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Cat ECS Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • IBC seismic certification
  • OSHPD pre-approval
One Safe Source
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Complete Specifications

Generator Set Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Standby Ratingtext4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Ratingtext3600 (no fan)/3500/3300 (no fan)/3180 ekW
Emissions/Fuel StrategytextLow Fuel, Tier 2
Voltagetext480 to 13800 Volts
Frequencytext60 Hz
Speedtext1800 rpm
Duty CycletextStandby, Mission Critical, Prime, Continuous
Maximum Ratingtext4000 ekW
Minimum Ratingtext3150 ekW
Engine ModeltextC175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Boremeasurement6.89in175mm
Strokemeasurement8.66in220mm
Displacementmeasurement6456.31in³105.8B
Compression Ratiotext15.3:1
AspirationtextTurbo Aftercooled
Fuel SystemtextCommon Rail
Governor TypetextADEM� A4
Length - Minimummeasurement262.5in6667mm
Length - Maximummeasurement331.1in8409mm
Width - Minimummeasurement92in2336mm
Width - Maximummeasurement128.5in3264mm
Height - Minimummeasurement99.8in2536mm
Height - Maximummeasurement150.7in3828mm
Dry Weight - Genset (minimum)measurement55100lb25000kg
Dry Weight - Genset (maximum)measurement66200lb30000kg

Standard Equipment

Air Inlet System

  • 4 x Single element air cleaner canisters with service indicator(s).

Control Panel

  • 24 Volt DC operation
  • 4 Programmable relay Inputs
  • 4 Programmable relay output
  • Alarm acknowledge
  • Amps (per phase & average)
  • Auto/start/stop control
  • Coolant temperature
  • DC volts
  • Digital indicators
  • Cat ECS 100
  • Emergency stop
  • Emergency stop pushbutton
  • Engine cool-down timer
  • Engine cycle crank
  • Environmental sealed front face
  • Failure to start (overcrank)
  • Frequency (Hz)
  • High Coolant temperature
  • Lamp test
  • Low coolant level
  • Low oil pressure
  • Oil pressure (psi, kPa or bar)
  • Operating hours
  • Overspeed
  • RPM
  • Speed adjust
  • Text alarm/event descriptions.
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • Volts (L-L & L-N)
  • Wall mounted controls:
  • Warning/shutdown Indicators:

Cooling System

  • AC Inlet: 6" ANSI / AC Outlet: 3-1/2" ANSI
  • Coolant sensors
  • JW Inlet: 6" ANSI / JW Outlet: 5" Cat Flange
  • SCAC cooling

Exhaust System

  • Dry exhaust manifold
  • Dual ANSI 18" / DIN 450 flanges. Shipped loose. Support required from installation

Fuel System

  • 10 Micron spin on yype
  • 4 Micron spin on type
  • Engine mounted filters x 3
  • Filters x 3
  • Primary fuel filter water/fuel water separator
  • Secondary/tertiary fuel filters

Generators and attachments

  • 3 Phase brushless
  • 3 Phase voltage sensing
  • 6 Leads
  • Anti-condensation space heater
  • Class H temperature rise at 40C ambient
  • Exciter diode monitor
  • Form wound
  • IEC platinum stator RTDs
  • Min / max exciter limiter
  • NEMA Class H insulation
  • Permanent magnet excitation (PMG)
  • Reactive droop capability
  • RFI suppression
  • Right side extension box, bottom cable entry
  • Salient pole
  • Voltage regulator

Governing System

  • ADEM A4
  • Redundant shutdown (Overspeed protection through a duplicate speed sensing system)

Lube System

  • Fumes disposal
  • Gear type lube oil pump
  • Integral lube Oil cooler
  • Lubricating oil
  • Oil drain lines and valve
  • Oil filter, filler and dipstick

Mounting Systems

  • Rails - Engine/generator
  • Rubber anti-vibration mounts - shipped loose

Starting / Charging System

  • Batteries and battery rack w/cables
  • Battery disconnect switch
  • Dual 24 volt electric starting motors

General

  • Paint - Caterpillar yellow with high gloss black rails
  • Right hand servicing
  • SAE standard rotation

Optional Equipment

Air Inlet Systems

  • Single element air cleaner

Control Panel

  • EMCP 4.4
  • Controller and MV and HV power connection locations
  • Controller voltage and current sensing groups
  • E-Stop
  • Generator harness
  • Generator temperature monitoring
  • Interconnect harness
  • Load share module
  • Modbus monitoring of packages
  • Speed adjust
  • Vandal proof panel door
  • Annunciator modules
  • Customer interface options

Cooling System

  • Fuel cooler
  • Package mounted radiators
  • Remote radiators

Crankcase Systems

  • Crankcase ventilation system
  • Explosive relief valves

Exhaust System

  • Exhaust collectors/manifold
  • Front housing - Prime or continuous
  • Front housing - Standby or mission critical
  • Mufflers (15, 25 and 34 dBA silencers)

Fuel System

  • Primary fuel filter

Generator

  • Anti-condensation heater
  • Internal excitation (IE)
  • Oversize and premium generators
  • Permanent magnet excitation (PMG)

Generators and Attachments

  • Differential current transformers
  • Generator air cleaner
  • Medium voltage - 3000 Frames - 60 Hz, 3 phase, 1800 rpm, FW, PM, No of leads=6, Pitch 0.6667
  • Thermostat for space heater

Instrumentation

  • Pyrometer and thermocouples

Lube System

  • Drain group oil pans
  • Electric prelube pumps
  • Lube oil heater
  • Lubricating oil
  • Oil filters

Mounting System

  • IBC vibration isolators - Shipped loose
  • Rubber anti-vibration mounts
  • Spring type linear vibration isolators

Power Termination

  • Circuit breakers, IEC compliant
  • Circuit breakers, UL listed

Special Tests / Reports

  • Custom generator TVA report
  • Generator test report
  • Genset fuel consumption test
  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor
  • Special test charge - Engine only
  • Standard engine test charge
  • Standard genset TVA (Torsional Vibration Analysis) report

Starting / Charging System

  • 20 Amp Battery chargers
  • 24 Volt battery set - Dry
  • 24 Volt electric starting motor
  • 35 Amp Battery chargers
  • 50 Amp Battery chargers
  • Air pressure regulator
  • Air starting motor
  • Charging alternators - Dry
  • Jacket water heaters
  • Starter location covers

General

  • Barring groups:
  • Control GP - air powered bar group
  • Engine air powered
  • Engine barring group
  • Manual
  • Special paint - 3500

Attachments