C2.2 (60 Hz)

C2.2 Generator Set

Producing reliable power from 15.5 to 20.0 ekW at 60 Hz, our C2.2 diesel generator sets designed to ISO 8528-5 transient response requirements. All C2.2 generator sets are R96/EUIIIa equivalent emissions compliant.

Product Images

Product Videos

Virtual Product Tour (VPT)

Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Maximum Ratingtext20.0 ekW
Standby Ratingtext13.6/15.5/17.6/20 ekW
Minimum Ratingtext15.5 ekW

View All Specifications (20)

Documents & Spec Sheets

Electric Power Ratings Guide

Download

DE14E3S 50 Hz 14.0 kVA, 60 Hz 17.0 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet

Download

DE13.5E3 50 Hz 18.0 kVA, 60 Hz 22.0 kVA, M Frame, EU IIIA Compliant Emissions Spec Sheet

Download

DE22E3 50 Hz 22.0 kVA, 60 Hz 25.0 kVA, M Frame, EU IIIA Emissions Compliant Spec Sheet

Download

DE14E3S 50 Hz 14.0 kVA, 60 Hz 17.0 kVA, LC Frame, EU IIIA Emissions Compliant Spec Sheet

Download

DE16E3S 50 Hz 16.5 kVA, 60 Hz 19.4 kVA, LC Frame, EU IIIA Emissions Compliant Spec Sheet

Download

DE18E3 50 Hz 18.0 kVA, 60 Hz 22.0 kVA, LC Frame, EU IIIA Emissions Compliant Spec Sheet

Download

DE22E3 50 Hz 22.0 kVA, 60 Hz 25.0 kVA, M Frame, EU IIIA Emissions Compliant Spec Sheet

Download

C1C2 Diesel Generator Set, 6.8 - 22 kVA, 50/60 Hz Spec Sheet

Download

C1C2 Diesel Generator Set, 6.8 - 22 kVA, 50/60 Hz Spec Sheet

Download

Features & Benefits

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
GCCP 1.3 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
  • Image may not be a representative of actual product
Cooling System
  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Cat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat® SOSSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.
One Safe Source
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Complete Specifications

Generator Set Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Maximum Ratingtext20.0 ekW
Standby Ratingtext13.6/15.5/17.6/20 ekW
Minimum Ratingtext15.5 ekW
Prime Power Ratingtext12.4/14/16/18 ekw
Emissions/Fuel StrategytextEU Stage IIIA
Voltagetext110 to 415 Volts
Frequencytext60 Hz
Speedtext1800 rpm
Duty CycletextStandby, Prime
Engine ModeltextCat® C2.2, In-line 4, 4-cycle diesel
Boremeasurement3.3in84mm
Strokemeasurement3.9in100mm
Displacementmeasurement135.2in³2.2l
Compression Ratiotext22.5:1
AspirationtextNaturally Aspirated
Fuel SystemtextIndirect Injection
Governor TypetextMechanical
Length - Maximummeasurement59.1in1500mm
Width - Maximummeasurement24.4in620mm
Height - Maximummeasurement43.9in1115mm

Standard Equipment

Air Inlet System

  • Air cleaner; light duty with disposable element

Control Panel

  • GCCP 1.3

Cooling System

  • Radiator and cooling fan with guards
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
  • Coolant drain line with valve

Exhaust System

  • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use - shipped loose

Fuel System

  • Standard open set fuel tank/base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank

Generators and Generator Attachments

  • IP23 Protection
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • 12 Leads
  • Segregated low voltage (AC/DC) wiring panel
  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry

Governing System

  • Mechanical governing system

Lube System

  • Oil drain line with valve
  • Lubricating oil

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant

Starting / Charging System

  • 12 Volt battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

Alternator Options

  • Coastal insulation protection

Certificates

  • Global certification for CIS
  • European upgrade to STD set for CE certificate

Circuit breakers

  • 4 Pole Circuit breaker
  • Padlockable breaker device

Control Panel Options

  • Volt free contacts for common alarm
  • Battery charger
  • Volt free contacts for genset running
  • Emergency stop with key
  • GCCP 1.3

Cooling System

  • Coolant heater

Enclosures

  • Single point lift for enclosure
  • Sound attenuated enclosure (GALV)
  • Aluminium
  • Steel

Fuel System

  • Skidbase for enclosures
  • DEFRA bunded fuel tank
  • Skidbase for open sets
  • Base feet
  • 1000 Hr extended service interval
  • Low fuel level alarm

Mounting Options

  • Battery removal
  • Industrial silencer removal
  • Silencer installation kit

Special Test and Inspection

  • PGS Test report @ 1.0 power factor

General

  • Packing case - canopied set
  • Radiator stone guard
  • Packing case - compact set

Attachments