C32B | 1500 kVA

C32B | 1250 kVA 50 Hz Generator Set

Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Our C32B generator sets are made for demands, so you can make yours.

Product Images

Product Videos

Virtual Product Tour (VPT)

Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Maximum Ratingtext1500 kVA
Minimum Ratingtext910 kVA
Emissions/Fuel StrategytextLow Fuel, Low Emissions

View All Specifications (23)

Documents & Spec Sheets

Electric Power Ratings Guide

Download

C32B, 50 Hz, 1250 kVA Standby 1100 ekW Prime, 910 kVA Cont., Low Fuel Consumption or Low Emissions Spec Sheet

Download

C32B, 50 Hz, 1500 kVA Standby 1375 ekW Prime, Low Fuel Consumption Spec Sheet

Download

Features & Benefits

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR500 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)
One Safe Source
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Complete Specifications

Generator Set Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Maximum Ratingtext1500 kVA
Minimum Ratingtext910 kVA
Emissions/Fuel StrategytextLow Fuel, Low Emissions
Voltagetext400 to 3300 Volts
Frequencytext50 Hz
Speedtext1500 rpm
Duty CycletextStandby, Mission Critical, Prime, Continuous
Engine ModeltextC32B TA, V-12, 4-Stroke Water-Cooled Diesel
Boremeasurement5.71in145mm
Strokemeasurement6.38in162mm
Displacementmeasurement1958.86in³32.1l
Compression Ratiotext15.0:1
AspirationtextTurbocharged, Air to Air Aftercooled
Fuel SystemtextMEUI
Governor TypetextAdem™A4
Length - Minimummeasurement164in4165mm
Length - Maximummeasurement176.6in4485mm
Width - Minimummeasurement66.3in1684mm
Width - Maximummeasurement87.8in2228mm
Height - Minimummeasurement85.1in2162mm
Height - Maximummeasurement86.4in2194mm
Dry Weight - Genset (minimum)measurement14700lb6668kg
Dry Weight - Genset (maximum)measurement17855lb8099kg

Standard Equipment

Air Inlet System

  • Single element canister type with service indicator

Control Panel

  • GCCP 1.3
  • GCCP 1.2
  • Control features
  • Programmable protective relaying functions
  • Digital indicators
  • Warning shutdowns
  • Communications

Cooling System

  • Fan and belt guards
  • Radiator fan and fan drive
  • ATAAC
  • Coolant drain line with valve
  • Caterpillar extended life coolant
  • Low coolant level sensor

Exhaust

  • Exhaust manifold - dry
  • 203 mm (8 in) ID round flanged outlet

Fuel System

  • Primary fuel filter with water separator
  • Fuel priming pump
  • Secondary fuel filters
  • Fuel cooler

Generators and Attachments

  • Integrated voltage regulator (IVR)
  • Permanent magnet excitation (PMG)
  • 3 Phase brushless
  • Reactive droop
  • Internal excitation (IE)
  • NEMA Class H insulation
  • Class H temperature rise at 40C ambient
  • Salient pole
  • Winding temperature detectors
  • 6 Lead
  • IEC standard hole pattern
  • Busbar connections, top center mounted, top cable entry

Governing System

  • ADEM(tm) A4

Mounting System

  • Rails - engine/generator/radiator mounting
  • Rubber anti-vibration mounts

Lube System

  • Oil drain lines and valve
  • Integral lube Oil cooler
  • Fumes disposal
  • Lubricating oil
  • Oil filter, filler and dipstick
  • Gear type lube oil pump

Power Termination

  • Busbar

Starting / Charging System

  • Battery disconnect switch
  • 45 Amp Charging alternator
  • 24 Volt electric starting motor
  • Battery, rack and cables

General

  • Caterpillar yellow with high gloss black rails & radiator
  • RH service
  • Flywheel and flywheel housing-SAE
  • SAE standard rotation

Optional Equipment

Air Inlet System

  • Dual element air cleaner
  • Heavy duty air cleaner
  • Standard air cleaners

Circuit breakers

  • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
  • Enclosures - Control packaging
  • Cable supports
  • Center posts busbars
  • Circuit breaker wiring groups
  • Power connection covers
  • Shrouds
  • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
  • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers

Control Panels

Control Panel

  • GCCP 1.3
  • Cat® ECS 100
  • Cat® ECS 200

Cooling System

  • Radiator duct flange
  • Certified radiator
  • High ambient radiator
  • Standard radiator
  • Extended life coolant

Enclosures

  • Enclosure fuel tank options
  • Sound attenuated enclosure
  • Enclosure louvres - fixed and motorized
  • Color options
  • AC Panel, outlets and lights
  • Premium sound attenuated enclosure
  • Cold weather bundle
  • Panel bracket
  • DC lighting package

Exhaust System

  • Exhaust through the wall kit
  • Flange and exhaust expanders
  • Flanges
  • Guard and shield system
  • All C32B engines have 203 mm (8 in) exhaust outlets
  • Elbow mounting kit
  • Mufflers
  • Flexible fittings

Generator and Attachments

  • Low voltage generators
  • Medium voltage generators

Lube System

  • Oil pan
  • Prelube manual sump pump
  • Oil level regulator

Mounting System

  • IBC vibration isolators
  • Mounting base types
  • Spring type vibration isolators
  • Standard package isolators

Power Termination

  • Circuit breakers, IEC compliant
  • Circuit breakers, UL listed

Power Connections

  • Low voltage connection cables
  • Neutral grounding connection
  • Center post busbars

Starting / Charging System

  • 10 Amp enclosure Battery charger
  • Space heater
  • 10 Amp Battery charger
  • 20 Amp Battery charger
  • 35 Amp Battery charger
  • Electric starting motor - Standard/heavy duty
  • Standard 24 volt open package battery set - Dry
  • Jacket water heater

Special Tests / Reports

  • PGS Test report @ 1.0 power factor
  • Standard engine test
  • Generator test report
  • Custom generator TVA report
  • PGS Test report @ 0.8 power factor
  • CSA test and certification
  • IBC seismic Certifications
  • Standard genset Torsional Vibration Analysis (TVA) report
  • OSHPD seismic Certifications

General

  • Special paint
  • US aid emblem

Attachments