D100 GC

D100 GC Generator Set

Producing reliable power of 100 ekW at 60 Hz, our D100 GC diesel generator sets designed to ISO 8528-5 transient response requirements. All D100 GC generator sets meet EPA Stationary Emergency (Tier 3) emissions standards.

Product Images

Product Videos

Virtual Product Tour (VPT)

Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Standby Ratingtext100 ekW
Maximum Ratingtext100 ekW
Minimum Ratingtext100 ekW

View All Specifications (20)

Documents & Spec Sheets

Electric Power Ratings Guide

Download

D100 GC, C4.4, 60 Hz 100 ekW, EPA Tier III Compliant Emissions Spec Sheet

Download

GCCP 1.2 Control Panel Data Sheet

Download

Cat® GC Generator Set Brochure for North America

Download

GCCP 1.5 Control Panel Data Sheet

Download

Features & Benefits

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
GCCP 1.2 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • UL 2200 Listed
  • ULC Certification Available
One Safe Source
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Complete Specifications

Generator Set Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Standby Ratingtext100 ekW
Maximum Ratingtext100 ekW
Minimum Ratingtext100 ekW
Frequencytext60 Hz
Emissions/Fuel StrategytextU.S. EPA Tier 3 Certified
Voltagetext208 to 600 Volts
Speedtext1800 rpm
Duty CycletextStandby
Engine ModeltextC4.4, In-line 4, 4-cycle diesel
Boremeasurement4.1in105mm
Strokemeasurement5in127mm
Displacementmeasurement269in³4.4l
Compression Ratiotext16.7:1
AspirationtextTurbocharged
Fuel SystemtextCommon Rail
Governor TypetextMechanical, ADEM™A4
Length - Maximummeasurement82.6in2097mm
Width - Maximummeasurement43.3in1100mm
Height - Maximummeasurement52.9in1343mm
Dry Weight - Genset (maximum)measurement2222lb1008kg

Standard Equipment

Air Inlet System

  • Air cleaner; light duty with disposable element
  • Air cleaner

Cooling System

  • Coolant drain line with valve
  • Radiator and cooling fan with guards
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive

Control Panel

  • GCCP 1.2 Control panel

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Fuel System

  • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank

Generator

  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • IP23 Protection
  • Tower panel, IP22, bottom cable entry
  • 12 Leads
  • Voltage regulator (single phase sensing)
  • Segregated low voltage (AC/DC) wiring panel

Governing System

  • Mechanical and electrical governing system - model dependent

Lube System

  • Lubricating oil
  • Oil drain line with valve

Mounting System

  • Termination points for coolant and lube oil drain lines
  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provision and drag points

Starting/Charging System

  • Batteries
  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

Alternator System

  • Anti-condensation heater
  • 3 phase sensing
  • Permanent magnet excitation (PMG)
  • R Frame auxilliary winding
  • Quadrature droop kit

Circuit breakers

  • Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A

Cooling System

  • Coolant heater
  • Low coolant temperature alarm
  • Low coolant level shutdown

Control Panel Options

  • Earth fault (2 wire only)
  • Control panel heater
  • GCCP 1.2 Control panel
  • Volt free contacts
  • Emergency stop with key
  • Voltage adjust potentiometer
  • Overload shutdown via breaker
  • Panel mounted audible alarm
  • Battery charger
  • Earth leakage (2 wire only)
  • Speed adjust potentiometer

Enclosures

  • Sound attenuated Level 2 enclosure

Fuel System

  • Low fuel level alarm
  • Bunded fuel tank
  • Low fuel level shutdown
  • High fuel level alarm

Mounting Options

  • Battery removal
  • Electronic governor
  • Industrial silencer
  • External single point lift - enclosure
  • Silencer installation kit

Special Packing/Inspectons for Shipment

  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor

General - Accessories / Miscellaneous

  • Packing case - canopied set
  • Packing case - compact set
  • Stone guards/rad trans flange

Attachments