DG175 GC (3 phase)

DG175-2 (3 phase)

The Cat® spark-ignited generator product line for stationary applications feature permanent magnet excitation, amortisseur winding, skewed stator, voltage adjustment through the EMCP controller, Class H winding insulation and 2/3 pitch incorporated.

Product Images

Product Videos

Virtual Product Tour (VPT)

Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Frequencytext60 Hz
Natural Gas Ratingtext175 eKW
Emissions/Fuel StrategytextU.S. EPA Certified for Stationary Emergency Application

View All Specifications (17)

Documents & Spec Sheets

Electric Power Rating guide

Download

DG175 GC Natural Gas Generator Set, 175 ekW 219 kVA 60 Hz

Download

DG175 GC to DG450 GC

Download

Gas Generator Set 50 and 60 Hz Ratings Guide

Download

Features & Benefits

Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
EMCP Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 Listed packages
  • CSA Certified
  • Certain restrictions may apply
  • Consult with your Cat® Dealer
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Complete Specifications

Generator Set Specifications

NameTypeValueUnit Value (Imperial)Unit NameUnit Value (Metric)Unit Name (Metric)
Frequencytext60 Hz
Natural Gas Ratingtext175 eKW
Emissions/Fuel StrategytextU.S. EPA Certified for Stationary Emergency Application
Speedtext1800 rpm
Engine ModeltextG14.2L Spark Ignited
Displacementmeasurement14.17in³864.71l
Fuel TypetextNatural Gas
Fuel SystemtextCarburetor, Down Draft
AspirationtextTurbocharged - Aftercooled
Governor TypetextElectronic
Compression Ratiotext9.5:1
Boremeasurement5.31in134.87mm
Strokemeasurement165.1mm6.5in
Lengthmeasurement3250mm127.95in
Widthmeasurement52.93in1344.5mm
Heightmeasurement1711.2mm67.37in
Weightmeasurement2610.9kg5756lb

Standard Equipment

Coolant

  • 50/50 Ethylene glycol antifreeze
  • Factory-installed radiator
  • Closed coolant recovery system

Fuel

  • Fuel pressure test po
  • Primary and secondary fuel shut-off
  • Low fuel pressure switch

Generator

  • Full load capacity alternator
  • Permanent magnet excitation
  • Class H insulation materia

Controls

  • EMCP 4.2 Series generator set controller

Mounting

  • Vibration isolaton (puck type)

Starting / Charging

  • Battery cables
  • Battery charging alternator
  • Solenoid activated starter motor
  • Engine electrical system

Optional Equipment

Generator

  • Thermal magnetic or electronic trip MCCBs
  • Anti-condensation heater
  • Shunt trip and auxiliary contact breaker

General

  • UL 2200 package
  • Enclosures: sound attenuated (L1 or L2), weather protective
  • CSA Certification
  • Dual Element or Heavy Duty air cleaner

Attachments