XQ1140 T4 Final - Diesel
The XQ1140 offers multiple modes of operation to meet your unique needs – even as they change. By incorporating two C18, EPA Tier 4 Final compliant diesel generator sets, this package can provide power output from the generator sets in parallel, N+1 power or independent power from each generator set. That versatility minimizes your operating costs always with the XQ1140 reliability and durability.
Product Images
Product Videos
Witness the Cat® XQ1140 Power Module
This US EPA Tier 4 Final power module features two Cat C18 generators packaged inside a 40 ft sound attenuated container. The XQ1140 is available for rent from your local Cat dealer.
Virtual Product Tour (VPT)
360° Exterior View
Virtual Product Tour
Specifications
| Name | Type | Value | Unit Value (Imperial) | Unit Name | Unit Value (Metric) | Unit Name (Metric) |
|---|---|---|---|---|---|---|
| Rating Prime | text | 910 ekW (1136 kVA) | ||||
| Frequency | text | 60 Hz | ||||
| Voltage | text | 120 - 600V |
Documents & Spec Sheets
Features & Benefits
Rental ready
Robust, durable product with a range of rental ready features to meet job requirements and applications.
Fuel/Emissions Strategy
Meets U.S. EPA Tier 4 Final emission standards and CARB certified for non-road mobile applications at all 60 Hz ratings.
Cat C18 Diesel Engines
Dual Cat C18 ACERT™ heavy-duty diesel engines. Industry proven reliability.
CAT EMCP 4.4 Digital Controls
Dual EMCP 4.4 easy to use digital controls with manual and automatic paralleling capability.
Cat LC Series Generators
Class H Insulation. Integrated voltage regular for fast response in demanding applications.
HMI Controls
Externally Mounted Color Touch-Screen HMI Control Center
Cat Connect
Remote monitoring for fleet management and asset tracking
Sound Attenuated Container
77 dBA @ 7m Sound Performance @ 75% Prime Load. 40' ISO high cube container, 9-high stack CSC certified Service and Personnel doors. Externally-accessible controls
500 hr oil change intervals
Reducing operating costs and producing less waste
Reduced Environmental Impact
110% Spill Containment of On-Board Engine Fluids.
Factory designed, built and tested
Single-source Supplier
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Additional options
Two-axle, air-ride traler with anti-lock brakesystem
Extended Service interval kits
600V generator
Extended Service interval kits
600V generator
Complete Specifications
Generator Set
| Name | Type | Value | Unit Value (Imperial) | Unit Name | Unit Value (Metric) | Unit Name (Metric) |
|---|---|---|---|---|---|---|
| Rating Prime | text | 910 ekW (1136 kVA) | ||||
| Frequency | text | 60 Hz | ||||
| Voltage | text | 120 - 600V | ||||
| Rating Standby | text | 1000 ekW (1250 kVA) | ||||
| Engine | text | Cat C18 | ||||
| Fuel | text | Diesel | ||||
| Height - Without Trailer | measurement | 114 | in | 2896 | mm | |
| Length - Without Trailer | measurement | 480 | in | 12192 | mm | |
| Width - Without Trailer | measurement | 96 | in | 2438 | mm | |
| Weight with Lube Oil and Coolant, Without Trailer | measurement | 50107 | lb | 22728 | kg | |
| 100% Load 60Hz | measurement | 66.4 | gal/hr | 252 | l/hr | |
| 75% Load 60Hz | measurement | 52.4 | gal/hr | 198 | l/hr | |
| 50% Load 60Hz | measurement | 38 | gal/hr | 144 | l/hr | |
| 100% Load 60Hz | measurement | 71.8 | gal/hr | 272 | l/hr | |
| 75% Load 60Hz | measurement | 56.6 | gal/hr | 214 | l/hr | |
| 50% Load 60Hz | measurement | 41 | gal/hr | 156 | l/hr | |
| Sound Power @ 7 meters (23 feet) @ All Ratings | text | 76 dB(A) |
Standard Equipment
Cat C18 Diesel Engines
- Two Cat C18 Diesel Engines
- Reliable, rugged, durable design
- EPA Tier 4 Final and CARB Emissions Certified
- Turbocharged Aftercooled
- Aftertreatment module. DEF System
Alternator and Alternator attachments
- 3 Phase, brushless, 12 lead, Permanent Magnet Excited
- LC6134G Frame
- Anti-condensation space heaters
- Integrated voltage regulator (IVR) with VAR/PF control
- Sized for 105°C temperature rise at 40°C ambient
Control Panels
- Dual EMCP 4.4 genset mounted digital controllers
- Externally accessible Color Touch-Screen HMI Control Center
- Manual and automatic paralleling capability
Governing system
- Electrical governing system ADEM™ A4
Cat Connect remote monitoring
- Provides package monitoring and management
Cooling System
- Vertically mounted radiator with vertical airdischarge from the container
- Provides 47°C ambient capability at Prime rating
Charging / Starting System
- UL Listed and CSA Certified 240V, 20 Amp battery charger
- Charging alternator; 24V-80A, heavy duty withintegral regulator and belt guards
- Solar maintainer for batteries
- Single electric starting motor, 24V per engine
Fuel System
- 630-gal (2385 L) double-wall fuel tank, UL 142and ULC 601 Listed and complies with Transport Canada requirements, internal and external fuel fill
- Fuel tanks connected by fuel transfer system withfilter to allow both engines access to all fuel on-board
- Primary and secondary fuel filters
- Fuel cooler
Air inlet system
- Heavy-duty air element, canister type
Distribution
- Externally accessible, Vibration Isolated, 3600A Frame, 1000 Ka, IC, 3-pole electrically operated breaker with lock out tag out provision
- Busbar connections
- Dual customer connections
Sound Attenuated Container
- 40' ISO high cube container
- Sound level is 76 dB(A) at 7 meters per SAEJ1074 measured at 75% prime load
- Sound attenuated air intake louvers and fivelockable personnel doors with panic release
Lube System
- Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve
- Oil drain line with internal brass ball valve routedto connection point accessible from exterior
General
- Factory tested and inspected
- Full manufacturer's warranty
- UL, NEMA, ISO, and IEEE standards
Optional Equipment
Trailer
- Two-axle, air-ride chassis with anti-lock brake system